Reference specifications for transmission cable
Item Unit Specifications
NOTES:
*1: Number of twist is not specified. However, it shall satisfy the electrical specifications such as
characteristic impedance, attenuation, etc. (Example: More than 40 times/m)
*2: Cross talk attenuation is applied when the twisted cable has 2 pairs (2 P).
Material is not specified. However, it shall be selected by considering the operating environment
(temperature, humidity) and the local regulation by the environment condition (ROHS directive, etc.).
Mechanical specification is not specified. However, it shall be selected by considering the operating
environment.
Never bundle transmission cable with power supply cable.
¢
Wiring rules
In the following cases, Signal amplifier is required.
When the total length of the transmission cable exceeded 500 m
AB + BC + BD + DE + EF > 500 m (Fig. 1)
When total number of the units is over 64.
When the total length of the transmission cable exceeded 500 m
Transmission cable length between each unit: 400 m
Total transmission cable length: 3,600 m (Fig. 2)
A
B
C
D
E
F
A
B
C
D
NS 1
NS 2
NS 4
NS 3
E
F
G
H
Transmission cable
Transmission cable
System
controller
Touch
panel
controller
Outdoor unit
Outdoor unit
Fig. 2Fig. 1
Indoor unit
Indoor unit
Terminal
resistor
Terminal resistor
When AB + BC + BD + DE + EF > 500 m,
signal amplifier is required.
Terminal
resistor
Touch
panel
controller
System
controller
Signal amplifier
NOTE: For details of maximum wiring length, refer to "VRF network system" on page 06-4.
4-3. Transmission cable - (06-56) - 4. Wiring design
SYSTEM
DESIGN
SYSTEM
DESIGN