• Remote controller address (Set F)
Maximum of 16 indoor units can be controlled by 1 individual remote controller with connecting
remote controller cable.
Those units connected with remote controller cable are regarded as a remote controller group.
Even there is only 1 indoor unit with one or no wired controller is connected, it is regarded as
one remote controller group.
– 3-wire type (Only for manual address setting):
00 01 0200 00 000 1 2 03 04 0500 00 003 0 0
*
1
3-wire type R. C.
R. C. line: 3 wire
3-wire type R. C.
*
2
*
2
00
Remote controller address
Rotary switch
Switch position
RC AD
0 0
1 1
2 2 •
3 3 •
4 4 •
5 5 •
6 6 •
7 7 •
8 8 •
9 9 •
10 A •
11 B
12 C •
13 D •
14 E •
15 F
*
1
: Set the remote controller address in order of 0, 1, 2, ..., 15. (Blank is now allowed.)
*
2
: When remote controller group is not constructed (1:1 connection of indoor unit and re-
mote controller), be sure that the remote controller address is set to the initial setting “0”
(factory setting).
– 2-wire type:
In initial starting up of this unit, addresses will be automatically set. Do not change the re-
mote controller address for the indoor unit. (Keep it at the initial setting “0”.)
1-3. Manual address setting method
- (07-11) - 1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS