Button name and function
Address code indicator on the remote controller and the operation lamp on IR receiver unit and on
the indoor unit are as shown in the figures below.
• For an outline of the address setting, refer to "Address setting" on page 07-4.
• For the details of function number and setting number used for the function setting, refer to "Func-
tion details" on page 07-108.
• It does not matter whether the refrigerant circuit address or indoor unit address is set first. (The
method shown here sets the indoor unit address first.)
• During address setting mode, indoor unit reject the any operation command from remote con-
troller.
MODE button
START/STOP button
TIMER set (-) button
TIMER set (+) button
FAN button
Setting number
Function number
01: Indoor unit address
02: Refrigerant circuit address
Indoor unit address valid range: 00 to 63
Refrigerant circut address valid range: 00 to 99
Switches between the setting number (bottom line)
and function number (top line)
Increases and decreases the displayed number
- Starts the address setting mode
- Changes the address indicator digits
Transmits address setting
Used to reconfirm the address setting
Used to confirm the address setting
Indication of address code
Indication of address data number (the right digit)
Indication of address data number (the left digit)
Long press (3 sec or more): Switches between the address setting mode
and the address setting complete mode
Short press: Switches the lamp indication
MANUAL
AUTO
Wireless remote controller
IR receiver unit Indoor unit
Indoor unit address display Refrigerant circuit address display
Operation lamp
ON
OFF
(Light continuously)
ON
OFF
(Light 1 sec. ON / 1 sec. OFF)
SET TEMP. "
p
" and "
q
" button
OPERATION lamp
TIMER lamp
FILTER lamp
MANUAL/AUTO button
RELATED LINKS
"Indoor unit (setting by wireless remote controller)" on page 07-87
1-4. Address setting by remote controller
- (07-17) - 1. System settings
FUNCTION
SETTINGS
FUNCTION