3. When “F3” is displayed on the LED104, press the ENTER button (SW109). Indicator on the
LED105 flashes.
LED105 LED104
LED105 LED104
4. Press the SELECT button (SW108) to display “10” on the LED105.
LED105 LED104
LED105 LED104
5. When “10” is displayed on the LED105, hold down the ENTER button (SW109) for 3 seconds
or longer. (Unless it is held down for at least 3 seconds, the selection will not be confirmed.)
When the automatic address setting function is activated, the display changes to “run.”
LED105 LED104
LED105 LED104
6. When the automatic address setting is completed, the number of signal amplifier is displayed
on the LED104. Verify that the count matches the number of signal amplifiers being installed.
LED105 LED104
LED105 LED104
Example: When 8 signal amplifiers are being connected
7. To exit the automatic address setting, press the ENTER button (SW109) in the setting complet-
ed status shown in the previous step.
LED105 LED104
LED105 LED104
8. To exit the function mode, press the MODE/EXIT button (SW107).
LED105 LED104
LED105 LED104
RELATED LINKS
"Signal amplifier" on page 07-133
1-5. Automatic address setting - (07-58) - 1. System settings
FUNCTION