LED105
code no.
Setting mode
LED104
code no.
Setting function
Factory
setting
Remarks
4 1
Low noise
mode setting
0 0 Off (Normal) ♦
0 1 On (Low noise mode)
4 2
Low noise
mode operation
level setting
0 0 Level 1 ♦
Level 1: The operating sound
lowers from about 3 to 5 dB (A)
more than the rated value.
0 1 Level 2
Level 2: The operating sound
lowers from about 3 to 5 dB (A)
more than the Level 1.
0 2 Prohibited
5 2 Prohibited 0 0 Prohibited ♦ Setting prohibited
5 3
Intelligent
refrigerant
control
0 0 Enable ♦
0 1 Disable
0 2
Enable only evaporation
temperature control
0 3
Enable only
condensation
temperature control
6 0 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
7 0
Electricity
meter no.
setting 1 *
1
0 0 Setting number x00 ♦
Set the ones digit and tens digit of
the number of the electricity meter
connected to CN135.
0 1 Setting number x01
•
•
•
•
•
•
•
•
•
9 8 Setting number x98
9 9 Setting number x99
7 1
Electricity
meter no.
setting 2 *
1
0 0 Setting number 0xx ♦
Set the hundreds digit of the
number of the electricity meter
connected to CN135.
0 1 Setting number 1xx
0 2 Setting number 2xx
7 2
Electricity
meter pulse
setting 1 *
2
0 0 Setting number xx00 ♦
Set the ones digit and tens digit of
the number of the electricity meter
pulse setting connected to CN135.
0 1 Setting number xx01
•
•
•
•
•
•
•
•
•
9 8 Setting number xx98
9 9 Setting number xx99
7 3
Electricity
meter pulse
setting 2 *
2
0 0 Setting number 00xx ♦
Set the hundreds digit and
thousands digit of the electricity
meter pulse setting connected to
CN135.
0 1 Setting number 01xx
•
•
•
•
•
•
•
•
•
9 8 Setting number 98xx
9 9 Setting number 99xx
9 0 Prohibited
0 0 Prohibited ♦
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
0 4 Prohibited
0 5 Prohibited
0 6 Prohibited
0 7 Prohibited
0 8 Prohibited
0 9 Prohibited
1 0 Prohibited
1 1 Prohibited
2-1. Setting on outdoor unit PCB - (07-72) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS