4. When the “Close” on the message screen is touched, the display returns to the R.C. Address
Setting screen. Turn on the power again.
Setting is reflected after the power is
turned on again.
Manual Addressing
Close
NOTES:
• Perform manual address setting only when setting the address with an arbitrary number. Indoor
unit remote controller address setting is necessary. Set the remote controller address of indoor
units connected by the same remote controller cable within a range of 1 to 9 and A (10) to F
(15) so that there is no duplication. (Do not set to “0”.)
• The address of this unit is set within a range of 1 to 32, but set it so that it does not duplicate the
remote controller address of an indoor unit connected by the same remote controller cable.
¢ Resetting the manual address setting number
1. Touch “Address Reset” on the R.C. Address Setting screen.
[001–05]
R.C.Address Setting
Current Address
Back
Manual Addressing
Address Reset
2. A verification screen is displayed. When the “Yes” is touched, a message screen is displayed.
No Yes
R.C.Address Setting
The address will be returned to factory
setting. OK?
3. When the “Close” on the message screen is touched, the display returns to the R.C. Address
Setting screen. Turn on the power again.
Setting is reflected after the power is
turned on again.
Manual Addressing
Close
2-16. Wired remote controller (Touch panel)
- (07-122) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS