Peak cut operation
Reduces the power consumption by setting a specific target value (maximum average power [kW])
for all the air conditioners and controlling operation so that this value is not exceeded.
Limit control is performed in 3 steps of “Step 1: Set temperature shift” → “Step 2: Thermostat OFF”
→ “Step 3: Outdoor unit stop”.
To perform this control, an electricity meter must be installed.
Normal
Actual power
consumption
Step 1
Step 2
Step 3
Group A
Group C
Group A Group B
Group C Group D
Group B
Group D
Group A Group B
Group C Group D
Group A Group B
Group C Group D
Grou
Grou
ON ON
ONOFF
Step 1
Set temperature shift
Step 2
Thermostat OFF
Step 3
Outdoor unit stop
Normal
Indoor units outside
the scope of energy
saving control
*Specifies the maximum average
electric power [kW] for the entire air
conditioning system.
1 period
Without control
Time Time
Electric power
Electric power
With control
Target maximum
average electric
power setting level
1 period 1 period
2-29. Energy saving setting on System controller