Outdoor unit connection interface (CN135) or touch panel controller connection interface
(TM201 CH1) to electricity meter
Item Specifications Remarks
Interface Dry contact “a” contacts
“a” contacts: ON when shorted
*
1
Pulse
Specifications
Width: 50 ms or more
Interval: 50 ms or more
Units 1 kWh/pulse (pulse units) recommended.
Constant
Considering the electricity meters available in
some countries, use of electricity meters with
3,200 pulse/kWh (pulse constant) or less
pulses are possible.
Line length restriction 150 m or less
Between electricity meter and
outdoor unit
Wiring specification
Control and instrumentation cable: CVV-S
(Control-use Vinyl insulated Vinyl sheathed
cable – Shielding) *
2
2-conductor: 1.25 mm
2
Line length restriction 25 m or less
Between electricity meter and
touch panel controller
Wiring specifications
2 core, twisted pair, 0.33 mm
2
(22 AWG) *
3
*
1
Pulse signal: normally OFF (open), ON (closed) when shorted
*
2
When affected by interference by induction, select shielded CVV cable (CVV-S cable). This is
because copper shielding tape is wrapped around CVV cable and induction interference from ad-
jacent power cables is alleviated and normal communication is maintained. In addition, when the
wiring is outdoors, select weather resistance cable.
*
3
Use cable in accordance with local regulations and rules for cable.
Number of installing electricity meters
Item Specifications Remarks
Number of installing electricity
meters
Max. 200
Per site (include Max. 4 VRF
systems)