Input signal type
The input signal type can be selected.
Edge
Emergency stop or All on
Ch1
Emergency stop reset or All off
Pulse
Emergency stop or All on Ch1
Emergency stop reset or All off Ch2
Electricity meter signal Ch1
When Edge is selected, only Ch1 can be used.
Control input function
• In case of Edge input:
Terminal Channel no. Input signal Command
TM201 Ch1
Off → On All on / Emergency stop
On → Off All off / Normal
Ch1
Indoor unit
All on / Emergency stop
On
300 ms or more
Off
All off / Normal
• In case of Pulse input:
Terminal Channel no. Input signal Command
TM201
Ch1
Pulse
All on / Emergency stop
Ch2 All off / Normal
Off
Off
On
On
TM201
Ch1
Ch2
Indoor unit
The width of pulse must be longer than 300 msec.
All on / Emergency stop
All off / Normal