1-8 745 Transformer Management Relay GE Power Management
1.2 TECHNICAL SPECIFICATIONS 1 PRODUCT OVERVIEW
1
OVERFREQUENCY (1 ELEMENT)
Operating Current Pickup: 0.05 to 1.00 in steps of 0.01 × CT
Operating Voltage Pickup 0.10 to 0.99 in steps of 0.01 × VT
Pickup Level: 50.01 to 65.00 in steps of 0.01 Hz
Dropout Level: Pickup – 0.03 Hz
Time Delay: 0.00 to 600.00 s in steps of 0.01 s
Signal Source: Winding 1 phase A current / voltage
Level Accuracy: ±0.02 Hz
Operate Time: Solid State Output: at 3% beyond pickup: 120 to 150 ms
Relay Outputs 2-5: at 3% beyond pickup: 125 to 155 ms (delay set to 0.0 s)
OVEREXCITATION ON VOLTS/HERTZ (2 ELEMENTS)
Operating Voltage Pickup: 0.10 to 0.99 in steps of 0.01 × VT
Pickup Level: 1.00 to 4.00 in steps of 0.01 V/Hz
Curve Shape: Definite Time (0.1 sec. base curve);
IEC Curve A/B/C
Time Delay: 0.00 to 600.00 s in steps of 0.01 s
Reset Delay: 0.0 to 6000.0 s in steps of 0.1 s
Signal Source: Voltage
Range: 10 to 65 Hz
Level Accuracy: ±0.02 V/Hz
Operate Time: Solid State Output: at 1.10 × pickup: 165 to 195 ms
Relay Outputs 2-5: at 1.10 × pickup: 170 to 200 ms (delay set to 0.0 s)
OVEREXCITATION ON 5
TH
HARMONIC LEVEL
Operating Current Pickup: 0.03 to 1.00 in steps of 0.01 × CT
Pickup Level: 0.1 to 99.9 in steps of 0.1%
Dropout: 95% of pickup
Time Delay: 0 to 60000 s in steps of 1 s
Signal Source: All phase currents
Operate Time: Solid State Output: at 1.10 × pickup: 20 to 120 ms
Relay Outputs 2-5: at 1.10 × pickup: 25 to 125 ms (delay set at 0.0 s)
INSULATION AGING: HOTTEST-SPOT LIMIT
Pickup Level: 50 to 300 in steps of 1°C
Delay: 0 to 60000 in steps of 1 min.
INSULATION AGING: AGING FACTOR LIMIT
Pickup Level: 1.1 to 10.0 in steps of 0.1
Delay: 0 to 60000 in steps of 1 min.
INSULATION AGING: LOSS OF LIFE LIMIT
Pickup Level: 0 to 20000 in steps of 1 x 10 h

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?

GE 745 TRANSFORMER MANAGEMENT RELAY Specifications

General IconGeneral
BrandGE
Model745 TRANSFORMER MANAGEMENT RELAY
CategoryRelays
LanguageEnglish

Related product manuals