GE Power Management 745 Transformer Management Relay 8-23
8 COMMUNICATIONS 8.3 MODBUS MEMORY MAP
8
DIFFERENTIAL
CURRENT
continued
02D3 Phase B Differential Current - Angle 0 to 359 1 ° Lag F1 ---
02D4 Phase C Differential Current - Magnitude 0.00 to 655.35 0.01 x CT F3 ---
02D5 Phase C Differential Current - Angle 0 to 359 1 ° Lag F1 ---
RESTRAINT
CURRENT
02D6 Phase A Restraint Current 0.00 to 655.35 0.01 x CT F3 ---
02D7 Phase B Restraint Current 0.00 to 655.35 0.01 x CT F3 ---
02D8 Phase C Restraint Current 0.00 to 655.35 0.01 x CT F3 ---
GROUND
DIFFERENTIAL
CURRENT
02D9 Winding 1 Ground Differential Current 0.000 to 65.535 0.001 x CT F53 ---
02DA Winding 2 Ground Differential Current 0.000 to 65.535 0.001 x CT F53 ---
02DB Winding 3 Ground Differential Current 0.000 to 65.535 0.001 x CT F53 ---
02DC Reserved
↓↓ ↓
↓↓↓ ↓
02DF Reserved
2ND
HARMONIC
02E0 Winding 1 Phase A 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E1 Winding 1 Phase B 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E2 Winding 1 Phase C 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E3 Winding 2 Phase A 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E4 Winding 2 Phase B 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E5 Winding 2 Phase C 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E6 Winding 3 Phase A 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E7 Winding 3 Phase B 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E8 Winding 3 Phase C 2nd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02E9 Reserved
↓↓ ↓
↓↓↓ ↓
02EF Reserved
3RD
HARMONIC
02F0 Winding 1 Phase A 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F1 Winding 1 Phase B 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F2 Winding 1 Phase C 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F3 Winding 2 Phase A 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F4 Winding 2 Phase B 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F5 Winding 2 Phase C 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F6 Winding 3 Phase A 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F7 Winding 3 Phase B 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F8 Winding 3 Phase C 3rd Harmonic Content 0.0 to 99.9 0.1 % Æ’o F2 ---
02F9 Reserved
↓↓ ↓
↓↓↓ ↓
02FF Reserved
Table 8–6: 745 MEMORY MAP (Sheet 7 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?

GE 745 TRANSFORMER MANAGEMENT RELAY Specifications

General IconGeneral
BrandGE
Model745 TRANSFORMER MANAGEMENT RELAY
CategoryRelays
LanguageEnglish

Related product manuals