GE Power Management 745 Transformer Management Relay 8-59
8 COMMUNICATIONS 8.3 MODBUS MEMORY MAP
8
WINDING 1
NEG SEQ TIME
O/C
2250 Winding 1 Neg Seq Time O/C Function --- --- --- F30 0 = Disabled
2251 Winding 1 Neg Seq Time O/C Target --- --- --- F46 1 = Latched
2252 Winding 1 Neg Seq Time O/C Pickup 0.05 to 20.00 0.01
×
CT F3 25 = 0.25
×
CT
2253 Winding 1 Neg Seq Time O/C Shape --- --- --- F36 0 = Ext Inverse
2254 Winding 1 Neg Seq Time O/C Multiplier 0.00 to 100.00 0.01 --- F3 100 = 1.00
2255 Winding 1 Neg Seq Time O/C Reset --- --- --- F68 1 = Linear
2256 Winding 1 Neg Seq Time O/C Block --- --- --- F87 0 = Disabled
2257 Reserved
↓↓ ↓
↓↓↓ ↓
225F Reserved
WINDING 2
NEG SEQ TIME
O/C
2260 Winding 2 Neg Seq Time O/C Function --- --- --- F30 0 = Disabled
2261 Winding 2 Neg Seq Time O/C Target --- --- --- F46 1 = Latched
2262 Winding 2 Neg Seq Time O/C Pickup 0.05 to 20.00 0.01
×
CT F3 25 = 0.25
×
CT
2263 Winding 2 Neg Seq Time O/C Shape --- --- --- F36 0 = Ext Inverse
2264 Winding 2 Neg Seq Time O/C Multiplier 0.00 to 100.00 0.01 --- F3 100 = 1.00
2265 Winding 2 Neg Seq Time O/C Reset --- --- --- F68 1 = Linear
2266 Winding 2 Neg Seq Time O/C Block --- --- --- F87 0 = Disabled
2267 Reserved
↓↓ ↓
↓↓↓ ↓
226F Reserved
WINDING 3
NEG SEQ TIME
O/C
2270 Winding 3 Neg Seq Time O/C Function --- --- --- F30 0 = Disabled
2271 Winding 3 Neg Seq Time O/C Target --- --- --- F46 1 = Latched
2272 Winding 3 Neg Seq Time O/C Pickup 0.05 to 20.00 0.01
×
CT F3 25 = 0.25
×
CT
2273 Winding 3 Neg Seq Time O/C Shape --- --- --- F36 0 = Ext Inverse
2274 Winding 3 Neg Seq Time O/C Multiplier 0.00 to 100.00 0.01 --- F3 100 = 1.00
2275 Winding 3 Neg Seq Time O/C Reset --- --- --- F68 1 = Linear
2276 Winding 3 Neg Seq Time O/C Block --- --- --- F87 0 = Disabled
2277 Reserved
↓↓ ↓
↓↓↓ ↓
227F Reserved
WINDING 1
NEG SEQ INST
O/C
2280 Winding 1 Neg Seq Inst O/C Function --- --- --- F30 0 = Disabled
2281 Winding 1 Neg Seq Inst O/C Target --- --- --- F46 1 = Latched
2282 Winding 1 Neg Seq Inst O/C Pickup 0.05 to 20.00 0.01
×
CT F3
1000=10.00
×
CT
2283 Winding 1 Neg Seq Inst O/C Delay 0 to 60000 1 ms F1 0 ms
2284 Winding 1 Neg Seq Inst O/C Block --- --- --- F87 0 = Disabled
2285 Reserved
↓↓ ↓
↓↓↓ ↓
228F Reserved
Table 8–6: 745 MEMORY MAP (Sheet 43 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT