GE Power Management 745 Transformer Management Relay 8-63
8 COMMUNICATIONS 8.3 MODBUS MEMORY MAP
8
WINDING 3
THD LEVEL
2340 Winding 3 THD Level Function --- --- --- F30 0 = Disabled
2341 Winding 3 THD Level Target --- --- --- F46 0 = Self-reset
2342 Winding 3 THD Level Min. Operating Current 0.03 to 1.00 0.01
×
CT F3 10 = 0.10
×
CT
2343 Winding 3 THD Level Pickup 0.1 to 50.0 0.1 % ƒo F2 500 = 50.0%
2344 Winding 3 THD Level Delay 0 to 60000 1 s F1 10 s
2345 Winding 3 THD Level Block --- --- --- F87 0 = Disabled
2346 Reserved
↓↓
↓↓
234F Reserved
WINDING 1
HARMONIC
DERATING
2350 Winding 1 Harm Derating Function --- --- --- F30 0 = Disabled
2351 Winding 1 Harm Derating Target --- --- --- F46 0 = Self-reset
2352
Winding 1 Harm Derating Min. Operating Current
0.03 to 1.00 0.01
×
CT F3 10 = 0.10
×
CT
2353 Winding 1 Harm Derating Pickup 0.01 to 0.98 0.01 --- F3 90 = 0.90
2354 Winding 1 Harm Derating Delay 0 to 60000 1 s F1 10 s
2355 Winding 1 Harm Derating Block --- --- --- F87 0 = Disabled
2356 Reserved
::
235F Reserved
WINDING 2
HARMONIC
DERATING
2360 Winding 2 Harm Derating Function --- --- --- F30 0 = Disabled
2361 Winding 2 Harm Derating Target --- --- --- F46 0 = Self-reset
2362
Winding 2 Harm Derating Min. Operating Current
0.03 to 1.00 0.01
×
CT F3 10 = 0.10
×
CT
2363 Winding 2 Harm Derating Pickup 0.01 to 0.98 0.01 --- F3 90 = 0.90
2364 Winding 2 Harm Derating Delay 0 to 60000 1 s F1 10 s
2365 Winding 2 Harm Derating Block --- --- --- F87 0 = Disabled
2366 Reserved
↓↓
↓↓
236F Reserved
WINDING 3
HARMONIC
DERATING
2370 Winding 3 Harm Derating Function --- --- --- F30 0 = Disabled
2371 Winding 3 Harm Derating Target --- --- --- F46 0 = Self-reset
2372
Winding 3 Harm Derating Min. Operating Current
0.03 to 1.00 0.01
×
CT F3 10 = 0.10
×
CT
2373 Winding 3 Harm Derating Pickup 0.01 to 0.98 0.01 --- F3 90 = 0.90
2374 Winding 3 Harm Derating Delay 0 to 60000 1 s F1 10 s
2375 Winding 3 Harm Derating Block --- --- --- F87 0 = Disabled
2376 Reserved
↓↓
↓↓
237F Reserved
Table 8–6: 745 MEMORY MAP (Sheet 47 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT

Table of Contents