11-10 745 Transformer Management Relay GE Power Management
11.1 COMMISSIONING SUMMARY 11 SETPOINT TABLES
11
W2 Ntrl Inst O/C 2 Pickup 10.00 x CT
W2 Ntrl Inst O/C 2 Delay 0 ms
W2 Ntrl Inst O/C 2 Block Disabled
W3 Ntrl Inst O/C 2 Function Disabled
W3 Ntrl Inst O/C 2 Target Latched
W3 Ntrl Inst O/C 2 Pickup 10.00 x CT
W3 Ntrl Inst O/C 2 Delay 0 ms
W3 Ntrl Inst O/C 2 Block Disabled
GROUND OVERCURRENT
W1 Gnd Time O/C Function Enabled
W1 Gnd Time O/C Target Latched
W1 Gnd Time O/C Pickup 0.85 x CT
W1 Gnd Time O/C Shape Ext Inverse
W1 Gnd Time O/C Multiplier 1.00
W1 Gnd Time O/C Reset Linear
W1 Gnd Time O/C Block Disabled
W2 Gnd Time O/C Function Disabled
W2 Gnd Time O/C Target Latched
W2 Gnd Time O/C Pickup 0.85 x CT
W2 Gnd Time O/C Shape Ext Inverse
W2 Gnd Time O/C Multiplier 1.00
W2 Gnd Time O/C Reset Linear
W2 Gnd Time O/C Block Disabled
W3 Gnd Time O/C Function Disabled
W3 Gnd Time O/C Target Latched
W3 Gnd Time O/C Pickup 0.85 x CT
W3 Gnd Time O/C Shape Ext Inverse
W3 Gnd Time O/C Multiplier 1.00
W3 Gnd Time O/C Reset Linear
W3 Gnd Time O/C Block Disabled
W1 Gnd Inst O/C 1 Function Disabled
W1 Gnd Inst O/C 1 Target Latched
W1 Gnd Inst O/C 1 Pickup 10.00 x CT
W1 Gnd Inst O/C 1 Delay 0 ms
W1 Gnd Inst O/C 1 Block Disabled
Table 11–6: S4 ELEMENTS (Sheet 5 of 12)
DESCRIPTION DEFAULT GROUP 1 GROUP 2 GROUP 3 GROUP 4