NetworX Version 3 Installation Manual
144
3 Keypad sounds upon AC Power Failure
4 Keypad sounds upon Low Battery Detection
5 Keypad sounds during Cross Zone Trip Time
6 Keypad sounds for Tamper Alarm
7 Keypad sounds for Emergency keys
8 Keypad sounds for Expander Trouble
SYSTEM TIMERS
Segment 1
Dynamic Battery Test duration (0-30 minutes)
0
Segment 2
AC Failure report delay (0-255 minutes)
60
Segment 3
Power Up Delay (0-60 seconds)
0
Segment 4
Siren Time (1-255 minutes)
3
Segment 5
Telephone Line Cut delay (0-255 seconds)
0
Segment 6
Cross Zone Time (0-255 minutes)
5
Segment 7
Chime Time in 50 ms increments (0-255)
5
Segment 8
Dialer delay (0-255 seconds)
0
Segment 9
Fire Alarm Verification Time (120-255 seconds)
0
Segment
10
Listen-In Time (0-255 seconds)
0
Segment
11
Zone monitor timer hours/days (0-255)
0
Segment
12
Auto arming warning timer (1-255 minutes)
1
Segment
13
Auto arming retry timer (1-255 minutes)
45
40
Segment
14
Programming timeout (1-255 minutes) (“0”=15 minutes)
0
USER CODE REQUIREMENTS
Segment 1 (Circle Numbers To Program)
1 Enables six digit code option. All arm/disarm/Go to program codes require six digits
2 Requires valid user code entry for site initiated downloading and panel initiated downloading
functions
3 Enables Auto Cancel / Abort
4 Reserved
5 On: keypad shutdown mode
6 On: user authorization to enter program mode
7 On: codes 16 and 17 are guard codes
41
8 Reserved
42 GO TO PROGRAM CODE
9-7-1-3-0-0
GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
Segment 1 (Circle Numbers To Program)
1 Reserved
2 Enables “Go To Program Code” as an arm only code
3 Enables “Go To Program Code” as an arm only code after closing
4 Enables “Go To Program Code” as a master arm/disarm code (can change user codes)
5 Enables “Go To Program Code” as an arm/disarm code
6 Enables “Go To Program Code” to bypass zones
7 Enables “Go To Program Code” opening and closing reports
43
8 Reserved