EasyManua.ls Logo

Global Fire JUNO NET - Power Requirements

Global Fire JUNO NET
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NEUTRO
FASE
1A
F
U
S
E
MEANWELL
MODEL: PS-65-27
INPUT: 100-240V AC 1.5A
OUTPUT: +27V 2.4A
50/60Hz
DANGER
220 VOLTS
NEUTRO
FASE
1A
F
U
S
E
2.4A POWER SUPPLY UNIT 5.6A POWER SUPPLY UNIT
Voltage
Current
Battery
EMC Standard EN55022 class B
EN61000-4-2,3,4,5,6,8,11
EN61000-3-2,3
2.4A PSU’s recommended for 1 or 3 loop stand-alone or networked panels.
5.6A PSU’s recommended for up to 9 loop self-contained or networked panels.
The maximum alarm sounder current is the power supply current (2.4A or 5.6A) less the panel's alarm current.
The maximum quiescent current per loop is 250mA. The loop short circuit (trip) current is 900mA.
Internal maximum 24V / 12AH
Primary supply voltage 230V AC +10%/-15%
MEANWELL
MODEL: LPP-150-27
INPUT: 85-264VAC ; 120-370VDC
OUTPUT: +27V 5.6A
47/63Hz
DANGER
220 VOLTS
POWER REQUIREMENTS
11
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013