CAUTION
Reset to normal operation all devices before applying power to the panel,
in particular manual call points.
In order to initiate the programming procedure of the SAM’s the Panel has to be in INSTALLATION MODE. See
function 8.4.1.
The enabling of this mode is done on a per loop basis. When a loop is in ASET MODE the TEST LED on the Main Panel,
will be illuminated. Should there be more than one loop in ASET MODE the TEST QUEUE button on the Main Panel
can be used to verify and display loops that are in this mode.
Although the system supports more than one loop being used in ASET MODE it is advisable to work with only one
loop in this mode at a time. This could help avoid problems with wrong devices being programmed or erased.
CAUTION
DO NOT remove or replace SAM’s while loop is powered. If one of these modules has to be replaced or removed, first
disconnect all supply sources to the panel.
CAUTION
Start SAM programming
Activate a blank SAM by either testing the device associated with it, either using the standard test procedure for the
device or by short-circuiting both SAM device wires (i.e. BLACK & RED) simulating in this case a device activation. Smoke
and heat detectors will have their alarm led permanently lit when activated. Sounders can be set to activate for
approximately 1 second, using function 7.3, every time a new SAM is activated (i.e. fire condition). Upon activation of the
conventional device and after a short delay (aprox. 3 seconds), the associated SAM is programmed with the next
available address. During this delay the panel will execute a verification, where the new address and device will be
confirmed and validated.
The programming of a new address can be monitored in four different ways, namely:
a) Using function 7.1, after a new SAM has been programmed the device count will increase by one and by selecting the
newly programmed address, the device type, address and analogue value can also be confirmed.
b) Using function 7.3, the user can select to activate the sounders when a device enters the alarm state. When in ASET
mode, the sounders will be activated for approximately one second, each time a device enters the fire condition and a
new SAM address has been programmed. This will only affect loops where the ASET MODE was enabled after entering
the SOUNDERS ON TEST ACTIVATION mode.
c) Using function 1.1, the log of events can be used to verify the devices that have been programmed.
d) Printer output, when present, its output will show an entry for each device that has been programmed with an
indication of device address and type.
Verify that there are no faults or fire conditions in the loop or system.
Clear all fault and fire conditions first.
A loop while in ASET mode will not offer any kind of protection against fire conditions.
Removal of a SAM while loop is powered can corrupt programming
of this module and all other SAM’s present in the loop.
6-4-1 Activate ASET Mode (SAM) - Only applies with Wizmart Protocol