In a self-contained panel of up to 12
loops, there is no requirement for an
RS485 Interface Board because the Sub-
Panels can be inter-connected via a TTL
bus.
The connections are made as follows:
CON1(J-NET-CON) to Cn4 (1st SUB-PANEL)
CN3 (1st SUB-PANEL) to CN4 (2nd SUB-PANEL)
Cn3 (2nd SUB-PANEL) to CN4 (3rd SUB-PANEL)
NOTE: There is no need to terminate
the last sub-panels’ CN3 because the
bus connection is a parallel one.
Connection Schematic for Self-Contained Panels
LOOPS 1 TO 3
LOOPS 4 TO 6
J-NET-LPCON
LOOPS 7 TO 9
LOOPS 10 TO 12
J-NET-CON
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
+ -+ -+ -+ -+ -+ -
J-NET-SP with LOOP-CARD
AUX 1
PSU
AUX 2
PSU
BELL 1 BELL 2
24v
BATT
EVAC
ZONE
MPX
OUT PF E SF24v0v 0v
0v
+ - + - + - + - + -
AUX PS
POWER SUPPLY IN
0V 0V 0V24V 28V 28VMON
BATT
24V
AUX PS
POWER SUPPLY IN
0V 0V 0V24V 28V 28VMON
BATT
24V
AUX PS
POWER SUPPLY IN
0V 0V 0V24V 28V 28VMON
BATT
24V
32
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013