Sounders - Disable & Assign
Sounder Configuration
Allows selection of PRESET or PROGRAMMED sounder operation.
Selecting PRESET (the default) will result in all sounders being operated; any Sounder Group settings will be ignored.
NOTE: the Sounder Groups must be defined before PROGRAMMED is selected because the
default group settings have all sounders set to silent.
NOTE: PRESET or PROGRAMMED does not affect any sounder delay settings.
Configure Sounder Groups
Allows all the Sounder Groups to be defined. A Sounder Group can consist of any combination of sounders. 512 Sounder
Groups can be defined.
First select the Sounder Group number then work your way through each panel.
For each panel you can select how each sounder reacts when that sounder group is activated.
For each sounder:
‘C’ indicates continuous operation.
‘S’ indicates silent (no) operation.
‘P’ indicates pulsing operation.
As you select different panels you will automatically only be offered the sounders that the particular panel can support
(although they may not physically be fitted).
Panel 00 corresponds to the main panel's conventional sounder circuits.
Group 512 is the Common Sounder Group. This is always operated when Sounder Group operation is turned on and a fire
occurs.
When a fire occurs all the Sounder Group information for the detector in fire is combined: the device Sounder Group is
combined with the Zone Sounder Group and the Common Sounder Group. ‘P’ pulsing will override ‘S’ silent and ‘C’ will
override ‘P’ pulsing.
When a subsequent fire occurs the new Sounder Group information is added to the existing Sounder Group information.
‘P’ pulsing will override ‘S’ silent and ‘C’ will override ‘P’ pulsing.
NOTES:
If Sounder Groups are defined then it is essential to set 4-1 Sounder Configuration to
PROGRAMMED, otherwise, all the system sounders will be activated by any fire event.
Individual detectors can be set not to activate Common Sounder Groups, Zone Sounder Groups or
all sounders. See function 4-5 Inhibit Sounders for Device.
If evacuate is operated (by setting CALL-POINTs to evacuate, then activating a CALL-POINT, for
example) the sounders will operate as if the sounder configuration were set to PRESET.
There is not room on the display to display help whilst using this function but help is available, as
usual, by pressing ‘:’, the colon key.