NOTE: disabled sounders are never activated by the evacuate timer.
Device Starts Evacuate Timer
Allows you to specify specific detectors that will start the Evacuate Timer.
The Evacuate Timer must be in DEVICE MODE to be activated by specific devices. See programming function 8-1-4.
Fire Brigade Delay Set-up
Allows the Fire Brigade Delay timer to be enabled and the duration of the delay to be set.
10 minutes is the maximum duration.
The timer can be set to:
DISABLED
ZONAL MODE
GLOBAL MODE
The triggering of the delay must also be specified, settings are:
CALL-POINTS ONLY - call-point start the delay, other devices cause immediate fire brigade output activation.
DETECTORS ONLY - any device that isn't a call-point starts the delay, call-points will cause immediate fire brigade
output activation.
ANY DEVICE - any device will start the delay.
If the function is set to ZONAL MODE it is also necessary to set up the activation using Function 3-6 Zone Fire Brigade
Delay Set-up.
For the Fire Brigade delay to operate the front panel ACTIVE DELAYS button has to be set to on.
NOTE: specific devices (function 6-1-6)can be set to override this delay.
Special Features Set-up
Programming functions associated with the system response and detection of a fire.
Two Devices to Evacuate
Enables or disables a system wide setting that detection of fire by two detectors automatically starts evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated immediately.
NOTE: disabled sounders will not be activated.