EasyManua.ls Logo

Global Fire JUNO NET - 1 Review Historic Log; Clear Historic Log; Display Historic Log; Print Historic Log Entries

Global Fire JUNO NET
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specific Functions
1
1-1
1-2
1-3
1-4
1-5
Review Historic Log
All the functions associated with reviewing or printing events and settings.
Display Historic Log
The panel logs all events in an internal event log. It can store a rolling 2000 entries. When it is full the latest entry is
added and the oldest entry discarded.
Help is automatically displayed on entry to the function because it is not possible to display a log entry and help at
the same time.
To select a specific entry, input the number and then press ENTER.
Print Historic Log Entries
Select which entries you wish to print and press ENTER.
If the printer is already in use it is necessary to wait until the printer is free before starting a new print job.
If you wish to stop a printout enter the function again and you will be given the option of canceling the printout.
This function cannot be accessed remotely (from a Repeater or the PC Graphics Interface).
Nothing will be printed if the printer is disabled by (function 8-4-3).
Note that once the log is full the log entry number (0001 - 2000) will change for each logged event but log entry
0001 will be the oldest entry and 2000 will be the most recent.
Clear Historic Log
Clears the Historic Log.
Print Loop/Device Set-up
Prints all the device information for the specified Analogue Loop. The information printed includes the device
address, type, zone, text label and whether it is currently disabled.
If the printer is already in use it is necessary to wait until the printer is free before starting a new print job.
If you wish to stop a printout enter the function again and you will be given the option of canceling the printout.
This function cannot be accessed remotely (from the PC Graphics software or a Repeater).
Nothing will be printed if the printer is disabled by (function 8-4-3).
Read/Clear Autostart Count
Every time the Main Panel has a Master Reset or it’s power is cycled the Autostart count is incremented. SYSTEM
RESETs from the front panel button do not increment the Autostart count.