AUXILIARY FIRE RELAYS (2) AND FAULT RELAY (1)
Two auxiliary fire relay outputs are provided on the J-NET-CON. These outputs are activated when a fire is detected
(unless specifically inhibited). They are labeled AUX1 and AUX2.
One auxiliary fault relay output is also provided on the J-NET-CON. This output is activated when a fault is detected.
Both Auxiliary Fire relays have Normally Open (NO) and Normally Closed (NC) contacts and a single Common (C)
connection. The Auxiliary Fault relay is energised (NC) while there are no faults present on the system and de-energised
(NO) when there is at least one fault on the system.
The contact ratings are : 1A, 50V AC/DC (min 100mA, 6V).
OPEN COLLECTOR REPEAT OUTPUTS
The J-NET-CON provides open-collector repeater outputs for activating Fire, Fault and Pre-alarm indicators.
These 3 outputs are rated at 100mA 24V DC max.
J-NET-CON
J-NET-CON
AUXILIARY FIRE
RELAY OUTPUTS
AUXILIARY FAULT
RELAY OUTPUT (NC)
NO
NO
NC
NC
NC
AUX 2FAULT AUX 1
C
C
C
PAL
FIR
REPEATS
FLT
OPEN-COLLECTOR
OUTPUTS
43
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL