4-6
4-7
Sounder Delay Set-up
Allows the sounder delay to be set-up:
The sounder delay can be set to GLOBAL MODE, ZONAL MODE or DISABLED.
The sounder delay period is defined (to a maximum of 10 minutes).
The devices that initiate a delayed sounder activation are specified.
If the function is set to ZONAL MODE it is also necessary to set up the activation using Function 3-5 Zone Sounder Delay
Set-up.
The options for initiation are:
CALL POINTS ONLY - call-points start the delay timer. The sounder groups associated with the activated call-point will be
queued for delayed activation. Other devices will not start the delay timer and will activate their sounder groups
immediately.
DETECTORS ONLY - detectors start the delay timer. The sounder groups associated with the activated detector will be
queued for delayed activation. Call points will not start the delay timer and will activate their sounder groups
immediately.
ANY DEVICE - any device will start the delay timer. The sounder groups associated with the activated device will be
queued for delayed activation.
For sounder delays to operate the front panel ACTIVE DELAYS LED has to be lit.
There is only one sounder delay timer so when this expires any further sounder activations will be immediate.
If ALARM SILENCE is pressed when there are sounders queued for delayed activation the queued sounders are also
silenced (stopped from sounding). Once the first alarm has been silenced by pressing ALARM SILENCE all subsequent
fires will be reported immediately (the sounder delay settings will be ignored).
NOTE: specific sounders (function 4-7) and specific detectors (function 6-1-6) can be set to
override this delay.
Override Sounder Delays
Allows specific sounders to activate immediately even if the system has been set with sounder delays active.
As you select different panels you will automatically only be offered the sounders that the particular panel can support
(although they may not physically be fitted).
0 indicates normal operation
X indicates that the specific sounder will operate immediately
Sounders set to immediate will also override any Sounder Group settings for that specific sounder. Sounders set to
immediate operation will sound continuously (pulsing settings will be overridden).
81
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL
globalfire.pt