SUB-PANEL BATTERIES
Make sure that those sub-panels that DO NOT have batteries connected DO have the resistor fitted across the battery
connection terminals. The resistor prevents the panel reporting a battery fault.
NOTE: arcing and fire risk. Never short circuit the battery terminals. Always connect the blue wire
between the batteries last.
24V
BATT
RED
BLACK
BLUE
NOTE: THE BATTERY CABLES
ARE OPPOSITE HANDED ON THE
SUB-PANEL BOARD COMPARED
TO THE CONNECTION BOARD.
J-NET-SP
47
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL