7-4
7-5
7-6
8
8-1
8-1-1
Test Zones
Select the Zones you wish to put into test mode.
Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
In test mode when a detector is activated the LED on the detector will be illuminated and the event will be reported on
the Main Panel (and Repeaters) for 15 seconds. If selected then the sounders will also operate for 1 second. The LED on
the detector is not latched and will clear when the alarm level falls below the alarm threshold for the device.
Pressing TEST QUEUE REVIEW will report the zones that are in Test Mode.
Sub-Panel LED Test
This function is used to confirm that all the Standard Sub-panel LEDs are functional.
Each of the LEDs on all sub-panels will operate in sequence.
The test is only performed whilst LED TEST MODE is shown within this programming function.
There is no need to press ENTER just use UP/DOWN to toggle between LED NORMAL MODE and LED TEST MODE.
This test has no effect on Integrated Sub-panels.
Upon exit of this programming function normal functionality is automatically restored.
Light LED on device
This function is used to confirm the physical location of a specific detector.
For each Sub-panel only one detector LED can be lit at any one time.
Select the device and SWITCHED ON and press ENTER. The device will typically take a few seconds to respond.
Selecting NORMAL for that device, or selecting SWITCHED ON for another device on the same Sub-panel, will clear the
LED on the first device.
General
Time/Date & Timers
Set Date & Time
Allows the date and time for the system to be set. The date and time is displayed on the LCD whilst the system is not in
fault or fire.
Press ENTER to skip an entry and after each entry.
It is important to set the date and time because it is used in the event logging and may also be used to change the
detector sensitivities or to disable delays at night.
There is only one clock in the system. Setting the date and time at a Repeater is actually setting the Main Panel clock.
92