Configure Timed Sensitivity
Allows the sensitivity to be set for day and night.
Settings are :
HIGH ( alarm threshold of 45)
NORMAL ( alarm threshold of 55)
LOW ( alarm threshold of 65
NOTE: Only detectors that have their sensitivity set to GLOBAL SENSITIVITY will have their
sensitivity changed, and then only if 6-1-8 Global Sensitivity Set-up has the day set to TIMED.
NOTE:
Other Device Options
Analogue Loop device settings that relate to a detector's sensitivity for both smoke & heat.
Select Device Heat Grade
This function is only applicable to Heat Detectors. It has no effect on other devices.
It allows the alarm threshold for the heat detector to be set.
The default threshold is 55 º C.
The Pre-alarm levels are always 10º C below the alarm thresholds.
Select Device Smoke Sensitivity
This function is only suitable for smoke detectors.
It allows the alarm threshold for smoke detectors to be set.
Each individual detector has the following settings:
NORMAL
LOW
HIGH
GLOBAL
If GLOBAL is selected then, depending the day, the appropriate HIGH, LOW, NORMAL or TIMED setting is used (see
functions 6-1-8 Global Sensitivity Set-up and 6-1-9 Configure Timed Sensitivity).
HIGH = 45
NORMAL = 55
LOW = 65
The Pre-alarm levels are always 10 below the alarm thresholds.
NOTE:
Detector
Detector
Detector )
Detectors set to LOW sensitivity do not meet the requirements of EN54 part 5.
Detectors set to LOW sensitivity do not meet the requirements of EN54 part 5.