Call Points to Evacuate
Enables or disables a system wide setting that a report of fire from a call-point automatically starts evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated immediately.
NOTE: disabled sounders will not be activated.
Memory
Programming functions that are associated with management of the Main Panel memory.
Clear Customer Flash Memory
This function erases all of the site specific data from the customer Flash memory on the SIM CARD. This is the majority of
the programmed settings.
DO NOT erase this data if you were supplied with pre-programmed site data.
It is not recommended that this function is carried out from a Repeater as the erase will take a few seconds and during
that time communication to the Repeater will be lost.
If the Customer Flash Memory is cleared:
}All Sounder Groups will have continuous sounder operation
}All Sounder Group definitions will be cleared
}The Sounder Configuration will be set to PRESET
}All Zone text will be cleared
}All Zone Sounder and I/O group settings will be cleared
}All Zone definitions will be cleared (no devices assigned)
}Zone sounder delay settings will be cleared
}The company name will be cleared
}All device text will be cleared
}All device specific settings will be cleared
}All sensitivity settings will be reset
}All delay settings will be cleared
}The language will be reset to English
}All I/O group definitions will be cleared
}User access to all programming functions will be denied
NOTE: the Installer Access Code will not be cleared.
After clearing the Customer Flash Memory it is essential to perform a system Master Reset to ensure the new settings are
sent to all sub-panels. (Settings are otherwise only sent when they are changed using the programming functions.)
> BEWARE, ENGINEERS ONLY