Detector Tests
If the devices have been assigned to Zones (on a pre-programmed SIM CARD or via the programming menus) then it is
possible to test the detectors with limited or no sounder operation.
Detector Tests By Zone
Before starting clear all faults, put the system into Active Mode, and press SYSTEM RESET.
Enter programming mode and select function 7-3 Sounders on Test Activation. This allows you to choose an audible
confirmation that a device has detected a fire. The audible confirmation consists of a 1 second period of sounder
operation.
ALL SOUNDERS ON DETECTOR TEST activates the Main Panel Conventional Sounders and all Conventional Sounders
and Loop Sounders on the Sub-panel under test.
SUB_PANEL SOUNDERS ON DETECTOR TEST only operates the Conventional Sounders and Loop Sounders on the Sub-
panel under test. I.e. The Sub-panel that the detector under test is physically connected to.
Now select function 7-4 Test Zones to select the Zones which will be tested.
Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
In test mode whenever a detector is activated the LED on that detector will be illuminated and the event will be reported
on the main panel for 15 seconds. If selected, the sounders will also operate for 1 second.
Pressing TEST (QUEUE REVIEW) will report the Zones that are in Test Mode.
Unassigned Detector Tests
If the detectors have not been assigned to a Zone then they can only be tested in normal (Active) mode. Using the
programming menu ensure the system is set to Active Mode then exit programming mode and press SYSTEM RESET.
Carry out a fire test on each detector. Confirm the LED lights on the detector under test. Confirm that the fire is reported
correctly at the Main Panel (and any Repeaters). Confirm that the sounders operate.
Note that sounders and detectors can be inhibited or delayed using the advanced features in the programming menus. If
the sounders do not operate as expected first verify all the settings for the sounders and the device under test.
66