Sounder Audibility Check
If the building is unoccupied then press SOUND ALARMS. All sounders should operate until the button is pressed again.
Confirm that this is the case.
Note that Apollo loop sounders may take a second or two to respond.
If the building is occupied it is strongly recommended that the test sounders functions in programming mode are used.
Enter programming mode and select 7-2 Test Sounders. Using this function, all the sounders can be checked.
Main Panel
The Main Panel Conventional Sounders will sound for 1 second then be silenced for 9 seconds.
Standard Sub-panels
Conventional Sounders and Loop Sounders are operated for 1 second then silenced for 9 seconds.
Integrated Sub-panels
Conventional Sounders and Loop Sounders are operated for 1 second then silenced for 9 seconds.
Conventional Sounder operation for a Repeater with Integrated Sub-panel will be synchronized to the Loop Sounder
operation.
63
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013