Device Set-up
Allows specific settings to be selected for individual Analogue Loop devices.
General
Settings common to all types of Analogue Loop devices.
Disable Loops
Allows a specific Analogue Loop to be disabled or enabled. The default is enabled.
All devices on disabled loops will cease to operate with the exception of the (audible) output from loop sounders.
Any loops that are disabled will also be indicated when programming mode is exited. They can then be reviewed using
the DISABLED (QUEUE REVIEW) button.
Device Disable
Allows a specific device to be disabled or enabled. The default is enabled.
Disabled devices have both inputs and outputs disabled.
This function does not disable the (audible) output from loop sounders.
Any devices that are disabled will also be indicated when programming mode is exited. They can then be reviewed using
the DISABLED (QUEUE REVIEW) button.
Set Selective Disablement
Allows a specific device to be set up for selective disablement.
The device is only disabled when the SELECTED DETECTORS (DISABLEMENTS) button on the front panel is activated.
This function is intended for use when certain detectors regularly need disabling but are not necessarily in the same
Zone.
Outside programming mode any devices that are currently disabled can then be reviewed using the DISABLED (QUEUE
REVIEW) button.
Set Device Reporting Details
Each detector can be set to:
FIRE
FAULT
PRE-ALARM
The default is FIRE reporting.
When the device is activated or reaches its alarm threshold then the event is reported in accordance with this setting.
Primarily intended for use with Input modules, it can allow activation of one input to trigger a fault report rather than
a fire.
NOTE: Transparency Configuration was added to this function. This configuration is ONLY
applied to Input/Output or Input units. It is not compliant to En54.
84
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL