Set Immediate Evacuate for Device
When a detector set to immediate evacuate reports a fire all Sounder Group settings are ignored. All sounders are
operated immediately as if the Sounder Configuration was set to PRESET and all delays are ignored.
NOTE: disabled sounders will not sound.
Device Activation Overrides Delays
Allows a detector to be set to override all zonal and global sounder, Fire Brigade Transmission and I/O delay timers.
When this device is activated the Fire Brigade Transmission is activated immediately and the Sounder Groups and I/O
Groups associated with this device are also activated immediately (even if they were already queued for delayed
activation).
However this device will not start any of the timers either which means that subsequent fires reported from other
detectors may experience the full delay duration (as programmed).
Inhibit Auxiliary Relays
Allows a specific detector to be set to not operate system I/O's when it reports a fire.
(Equivalent to pressing auxiliary relays disablement button.)
Global Sensitivity Set-up
This function selects the sensitivity of all the detectors that have been set to GLOBAL SENSITIVITY.
Different settings can be entered for weekdays and for Saturday and Sunday.
Settings are :
HIGH ( alarm threshold of 45)
NORMAL ( alarm threshold of 55)
LOW ( alarm threshold of 65
TIMED
If TIMED is selected then the night and day sensitivity settings used are based on whether it is night or day.
Set the night and day sensitivities using programming function 6-1-9. Define the time day and night start using
programming function 8-1-2.
The Pre-alarm levels are always 10 below the alarm thresholds.
Ensure that the system clock day, date and time are set correctly (function 8-1-1).
Note that in order to keep day/night and day settings consistent a day setting starts at sunrise (which is set by function 8-
1-2). This means that, for example, the Saturday setting will start at 8:00 AM on Saturday.
NOTE:
Detector
Detector
Detector )
Detectors set to LOW sensitivity do not meet the requirements of EN54 part 5.
85
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL