8-1-2
8-1-3
8-1-4
Define Day & Night
Defines sunrise and sunset for the system.
The system considers a day to start at sunrise. So when different detector sensitivities are set for different days (function
6-1-8) the new day will start at the sunrise time defined here.
If different sensitivities have been set for day and night (function 6-1-9) then the times defined here are the times the
sensitivity change will take place.
If delays have been set to be switched off at night (function 8-1-3) then this will happen at the sunset time defined here.
Delays Off at Night
This function allows the delays for Sounders, I/O activation and Fire Brigade Transmission to be overridden at night.
There are two options: OFF and UNAFFECTED.
UNAFFECTED means that the system settings will remain the same at night as they are during the day.
OFF means that at night time the Sounder, I/O module and Fire Brigade Transmission delays are all turned off and the
outputs will activate immediately a fire is detected.
This function has exactly the same effect as using the ACTIVE DELAYS button on the front panel to disable the delays at
sunset, then using the same button to restore the day setting at sunrise.
Sunrise and sunset are defined using function 8-1-2.
Configure Evacuate Timer
Allows the evacuate timer to be enabled and the duration of the timer to be set.
The evacuate timer runs in parallel to all other events. Once triggered it starts counting down, when it expires all
sounders are activated. This means various sounder groups may be activated in the meantime (and even silenced)
but when the evacuate timer expires all sounders not sounding are activated.
10 minutes is the maximum duration.
The Evacuate Timer can be set to:
DISABLED
DEVICE MODE
GLOBAL MODE
In DEVICE MODE the evacuate timer is started when a device that has been configured to start the Evacuate Timer
detects a fire.
In GLOBAL MODE the Evacuate Timer is started when any device detects a fire.
NOTE: for DEVICE MODE to work at least one device must be set to start the timer. See
programming function 8-1-5.
NOTE: once started the evacuate timer is not stopped by pressing ALARM SILENCE, although
ALARM SILENCE will still silence the sounders once they have been activated.
93
Manufacturers of Fire Detection Equipment
INSTALLATION & COMMISSIONING MANUAL REVISION 4.0 05/2013
JUNO NET - NETWORKABLE ADRESSABLE PANEL