Learning Which Devices Are Fitted
Enter programming mode.
If site specific data has NOT been pre-programmed then select function 8-3-1 Clear Customer Flash Memory and clear
the customer flash. (You must NOT do this if you have been supplied with a SIM CARD pre-programmed with your site
data.)
Select function 8-3-2 Clear Non-Volatile RAM and clear the NVRAM.
Exit Programming mode.
Press SYSTEM RESET.
Wait 90 seconds for the system to automatically learn which devices are present and report any faults.
(A SYSTEM RESET or Master Reset in Installation Mode results in an analogue loop power off period of 8 seconds [reset],
an analogue loop charge up of 15 seconds then commencement of loop polling.
Review the faults (using the FAULT (QUEUE REVIEW) key if there is more than one). Note down the messages then remove
power and rectify the faults.
Power up the system, let it initialize and enter programming mode.
Select function 7-1 Device Count, Type and Value
Using the +/- keys to select the loop number and 0-9 or to select the device confirm that all Sub-panels and
devices are present.
Once all faults have been cleared and the system has been in Installation Mode for 90 seconds then the system can be put
into Active Mode.
Note that there is no clear end to Installation mode because the system is constantly looking and learning. However if the
system is put into Active Mode and Installation Mode hasn’t had time to identify all system components you will very
quickly be greeted with error reports regarding unexpected devices.
If devices are ever removed, replaced or added then Installation Mode must be selected so that the system can learn the
new configuration. If you do not do this the system will report a fault.
NOTE: New SAM’s (Self Addressable Modules) need a different installation process because they
need to be assigned addresses before the panel can learn that they are present. This procedure is
covered later in this manual in the section entitled “6-4 Automatic Address Setting (SAM)”.