REPEATERS
Repeaters are installed in a similar manner to the Main Panel.
Mini Rep repeaters are supplied by an external 24Vdc, normally from the control panel.
The Repeater should be located where access to the internal components is not restricted and where the unit is not
exposed to high levels of moisture, vibration and shock.
Avoid placing the Repeater in direct sunlight as this may impair programming using the infra-red keypad.
Any metal swarf could damage the PCBs if it is still present when the Repeater is powered up so it is recommended
that all PCBs are removed from the box whilst the box is being installed. Make a note of the positions of the PCBs
before removal.
WARNING: observe ESD precautions when handling the PCBs.
Mains Power Connection
The Repeater must be earthed.
The LIVE connection must be made to the fused input on the power supply module. This input will also have a BLACK
or BROWN wire leading into the power supply unit.
The connector with a BLUE wire leading into the power supply unit is the NEUTRAL.
Integrated Sub-panels
A Repeater may have an Integrated Sub-panel. To enable the Integrated Sub-panel a Loopcard must be fitted to the
Repeater PCB. The Loopcard is secured on to 4 pillars behind the LCD module.
You may fit a 1 or 3 loop Loopcard.
If the Loopcard is fitted an ANALOGUE LOOP CONNECTION BOARD is also required. This is mounted inside the
Repeater box and requires a cable form between it and the Repeater PCB.
Ensure all connectors are correctly aligned.
ELECTRO-STATIC SENSITIVE DEVICES (ESD)
TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR
INSTALLING PRINTED CIRCUIT BOARDS.