F 5220 (0625)
266
Resolution 24 Bit
Accuracy gate time measuring:
±0.5% over the complete range
pulse measuring: without loss of any pulse
Gate time n
∗ 50 ms (n = 0...65,535)
Min. pulse length 500 ns
Line length 500 m, screened, twisted pair (for 100 kHz)
Space requirement 4 SU
Operating data 5 VDC / 200 mA
24 VDC / 500 mA plus load
Outputs 2 with integrated safety shutdown,
1 output related to each input,
switchable independent from the PES cycle;
monitoring of the lines for short-circuit and line break SIL 1..SIL2
(evaluation only for used signals)
Allowable line resistance 11
Ω max.
(forward and return line)
• Output power 500 mA, 24 VDC
• short-circuit current 0.75...1.5 A
• line break 0.5...9.5 mA
• output leakage
current 350 µA max.
• length of the
test signal 200 µs max.
Reaction time
• gate time measuring: 50 ms typical
(depends on application: speed of the rotation variation)
• pulse measuring: <100 µs
verified during the safety time of the counter module
The error codes for the module are shown in the display of the corresponding central
module. For further informations see operating system manual.
The parameterization of the module must also be performed according to the operating system
manual for the currently used version of the operating system. Especially the chapter about the
noise blanking has to be regarded.
Setting: Safety time
≥ 3 x watchdog time.