F 6220 (0625)
299
Type B
Thermocouple Pt30%Rh/Pt6%Rh
Nominal range:
Input voltage 0.092 mV... 13.820 mV
Temperature limits 150 °C...1820 °C
Monitored
Range of use:
Input voltage 0.002 mV...13.820 mV
Temperature limits 50 °C... 820 °C
Value in ELOP II +500...+18200 (variable type INT)
Type
J
Thermocouple Fe/CuNi
Nominal range:
Input voltage -8.095 mV...69.553 mV
Temperature limits -210 °C...1200 °C
Monitored
Range of use:
Input voltage -8.095 mV... 69.553 mV
Temperature limits -210 °C...1200 °C
Value in ELOP II -2100...+12000 (variable type INT)
Type
K
Thermocouple CrNi/NiAl
Nominal range:
Input voltage -6.035 mV...54.819 mV
Temperature limits -210 °C...1370 °C
Monitored
Range of use:
Input voltage -6.458 mV...54.819 mV
Temperature limits -270 °C...1370 °C
Value in ELOP II -2700...+13700 (variable type INT)
Type
T
Thermocouple Cu/CuNi
Nominal range:
Input voltage -5.753 mV...21.003 mV
Temperature limits -210 °C...400 °C
Monitored
Range of use:
Input voltage -6.258 mV...21.003 mV
Temperature limits -270 °C...400 °C
Value in ELOP II -2700...+4000 (variable type INT)
Type
E
Thermocouple CrNi/CuNi
Nominal range:
Input voltage -9.063 mV... 76.373 mV
Temperature limits -210 °C...1000 °C
Monitored
Range of use:
Input voltage -9.835 mV... 76.373 mV
Temperature limits -270 °C...1000 °C
Value in ELOP II -2700...+10000 (variable type INT)