F 6221 (0625)
319
• Cable type: Z 7063/6221/ExCn/U1V part no. 93 6221 100
Z 7063/6221/ExCn/I part no. 93 6221 105
Note The grounds (I1- to I8-) are joined to a common ground (I-). The sig-
nals (I1- to I8-) may only be interconnected on the module. No external
joints are allowed.
The pins d4 and d30 on the front socket of the F 6221 are omitted
(coding of the front plug). Pin allocations refer to the connections on
the printed circuit board in the front plug.
In Ex applications, the cable shield has to be connected to the equipo-
tential bonding. In non Ex applications, the cable shield is connected
to the PE terminal / bus bar on the subrack.
Channel Connection Color
I1+
I1-
z2
d2
WH
BN
I2+
I2-
z4
d4
GN
YE
I3+
I3-
z6
d6
GY
PK
I4+
I4-
z8
d8
BU
RD
I5+
I5-
z10
d10
BK
VT
I6+
I6-
z12
d12
GY-PK
RD-BU
I7+
I7-
z14
d14
WH-GN
BN-GN
I8+
I8-
z16
d16
WH-YE
YE-BN
Cable screen YEGN
Channel Connection Color
TC1+
I1-
z18
d2
WH-GY
GY-BN
TC2+
I2-
z20
d4
WH-PK
PK-BN
TC3+
I3-
z22
d6
WH-BU
BN-BU
TC4+
I4-
z24
d8
WH-RD
BN-RD
TC5+
I5-
z26
d10
WH-BK
BN-BK
TC6+
I6-
z28
d12
GY-GN
YE-GY
TC7+
I7-
z30
d14
PK-GN
YE-PK
TC8+
I8-
z32
d16
GN-BU
YE-BU
Cable screen YEGN
Cable
LiYCY
16x2 x 0.2 mm
2
screened
Channels (I1+ to I8+) for
input signal measuring
Channels (TC1+ to TC8+) for
supply voltage monitoring