F 8627X (0650)
361
4 Functions of the switches
4.1 Functions of switch 1 (S1)
Table 5: Functions of switch 1 (S1)
S1 ON OFF Description
1 10 ms 0 ms The "Timeout" is the timeframe within which the receiver
must acknowledge receiving packets from the transmitter.
It is set via the switches S1/1-5.
Standard value: 10 ms (switch 1/1-5 "OFF").
Switches S1/1-5 can be combined by the user.
10 ms must be added for each combination of switches.
HIPRO-S-DIRECT must be activated
(switch 1/7 "ON").
2 20 ms 0 ms
3 40 ms 0 ms
4 400 ms 0 ms
5 1000 ms 0 ms
6ID_IP
ON
ID_IP
OFF
For OS versions < 4.x no function
(See also Chapter 5.2.3)
ID_IP ON
The bus station number (ID) which is set on the F 865x
central module via switches (S1 1-7) is used as Res-ID if
no Res-ID could be determined from the loaded user pro-
gram.
ID_IP OFF
The bus station number (ID) which is set on the F 865x
central module via switches (S1 1-7) is never used for the
Res-ID.
7DIRECT
Mode
enabled
DIRECT
Mode
disabled
HIPRO-S-DIRECT Mode must be activated if more than
one bus configuration is required. HIPRO-S-DIRECT is
supported beginning with the F 8627X OS version 3.x.
8 Passive
Mode
disabled
Passive
Mode
enabled
The Passive Mode controls the communication to the
HIMA OPC server.
Passive Mode enabled:
The Token Passing between the F 8627X to the HIMA
OPC servers is disabled.
The HIMA OPC servers cyclically exchange data with the
F 8627X, independent of the token owner.
Passive Mode disabled:
The Token Passing between the F 8627X and the HIMA
OPC servers is enabled.
The HIMA OPC servers only exchange data with the
F 8627X if they have the Token.