IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 147
Receivers Compatible with the Control Panel Reporting
SBUS Class A supervision lost ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS Class A supervision restore ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
SBUS expander trouble ET Exp. ID ETNNXX0000 1 333 Exp. ID 000
SBUS expander trouble restore ER Exp. ID ERNNXX0000 3 333 Exp. ID 000
SLC class A supervision trouble ET Exp. ID ETNNXX0000 1 331 Exp. ID 000
SLC class A supervision trouble restore ER Exp. ID ERNNXX0000 3 331 Exp. ID 000
SLC programming ended, system active TE 0 TENN000000 3 607 00 000
SLC programming started, system shut
down
TS 0 TSNN000000 1 607 00 000
SLC short circuit trouble ET Exp. ID ETNNXX0000 1 332 Exp. ID 000
SLC short circuit trouble restore ER Exp. ID ERNNXX0000 3 332 Exp. ID 000
Time changed event JT 0 JTNN000000 1 625 00 000
Unable to report to account trouble RT Receiver # RTNN00RRRR 1 354 00 Receiver
#
Unable to report to account trouble restore YK Receiver # YKNN00RRRR 3 354 00 Receiver
#
User access code changed JV 0 JVNN000000 1 602 00 000
User initiated manual dialer test RX 0 RXNN000000 1 601 00 000
Walk test begin TS 0 TSNN000000 1 607 00 000
Walk test end TE 0 TENN000000 3 607 00 000
Zone Events Zone events are reported only when “Report by Zone” is selected
Auxiliary power trouble FT 0000 FTNN000000 1 320 00 000
Auxiliary power trouble restore FJ 0000 FJNN000000 3 320 00 000
CO Detector Alarm GA Zone # GANN000ZZZ 1 162 00 Zone #
CO Detector Alarm Restore GH Zone # GHNN000ZZZ 3 162 00 Zone #
CO Detector Supervisory Alarm GS Zone # GSNN000ZZZ 1 200 00 Zone #
CO Detector Supervisory Alarm Restore GR Zone # GRNN000ZZZ 3 200 00 Zone #
CO Detector Trouble GT Zone # GTNN000ZZZ 1 373 00 Zone #
CO Detector Trouble Restore GJ Zone # GJNN000ZZZ 3 373 00 Zone #
Detector Alarm FA Zone # FANN000ZZZ 1 110 00 Zone #
Detector Alarm Restore FH Zone # FHNN000ZZZ 3 110 00 Zone #
Detector trouble FT Zone # FTNN000ZZZ 1 373 00 Zone #
Detector trouble restore FJ Zone # FJNN000ZZZ 3 373 00 Zone #
ECS Switch Trouble QT 0 QTNN000000 1 242 00 000
ECS Switch Trouble Restore QJ 0 QJNN000000 3 242 00 000
ECS Supervisory/Tamper Alarm QS 0 QSNN000000 1 241 00 000
ECS Supervisory/Tamper Alarm Restore QR 0 QRNN000000 3 241 00 000
ECS Output Group Trouble QT Group # +1000 QTNN001GGG 1 320 00 Group #
ECS Output Group Trouble Restore QJ Group # +1000 QJNN001GGG 3 320 00 Group #
External Reset/Silence/Fire Drill switch
trouble
UT 0000 UTNN000000 1 373 00 000
External Reset/Silence/Fire Drill switch
trouble restore
UJ 0000 UJNN000000 3 373 00 000
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID #
(If Any)
SIA
Event
Code
s
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.2 Report Formats Table (Continued)