148 IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Reporting Receivers Compatible with the Control Panel
LOC Mic Activated ECS Alarm QA 0 QANN000000 1 220 00 000
LOC Mic Activated ECS Alarm Restore QH 0 QHNN000000 3 220 00 000
LOC/Point ECS # Alarm QA Emergency # QANN0E0000 1 220 +
Emergen
cy #
00 000
LOC/Point ECS # Alarm Restore QH Emergency # QHNN0E0000 3 220 +
Emergen
cy #
00 000
Manual pull switch alarm FA Zone # FANN000ZZZ 1 115 00 Zone #
Manual pull switch alarm restore FH Zone # FHNN000ZZZ 3 115 00 Zone #
Manual pull switch trouble FT Zone # FTNN000ZZZ 1 373 00 Zone #
Manual pull switch trouble restore FJ Zone # FJNN000ZZZ 3 373 00 Zone #
Notification output trouble FT Group # + 1000 FTNN001GGG 1 320 00 Group #
Notification output trouble restore FJ Group # + 1000 FJNN001GGG 3 320 00 Group #
Positive Alarm Sequence acknowledge
switch trouble
FT Zone # FTNN000ZZZ 1 373 00 Zone #
Positive Alarm Sequence acknowledge
switch trouble restore
FJ Zone # FJNN000ZZZ 3 373 00 Zone #
SLC LED Module trouble ET 0000 ETNN000000 1 333 00 000
SLC LED Module trouble restore ER 0000 ERNN000000 3 333 00 000
Status Point Types Trouble UT 0 UTNN000000 1 379 00 000
Status Point Types Trouble Restore UJ 0 UJNN000000 3 379 00 000
Supervisory Detector Alarm FS Zone # FSNN000ZZZ 1 200 00 Zone #
Supervisory Detector Alarm Restore FR Zone # FRNN000ZZZ 3 200 00 Zone #
Supervisory/Tamper Alarm FS Zone # FSNN000ZZZ 1 200 00 Zone #
Supervisory/Tamper alarm condition restore FR Zone # FRNN000ZZZ 3 200 00 Zone #
Supervisory/Tamper switch trouble FT Zone # FTNN000ZZZ 1 373 00 Zone #
Supervisory/Tamper switch trouble restore FJ Zone # FJNN000ZZZ 3 373 00 Zone #
System-based AUX1 switch alarm UA 1000 UANN001000 1 140 01 000
System-based AUX1 switch alarm restore UH 1000 UHNN001000 3 140 01 000
System-based AUX1 switch trouble UT 1000 UTNN001000 1 373 01 000
System-based AUX1 switch trouble restore UJ 1000 UJNN001000 3 373 01 000
System-based AUX2 switch alarm UA 2000 UANN002000 1 140 02 000
System-based AUX2 switch alarm restore UH 2000 UHNN002000 3 140 02 000
System-based AUX2 switch trouble UT 2000 UTNN002000 1 373 02 000
System-based AUX2 switch trouble restore UJ 2000 UJNN002000 3 373 02 000
Voice Aux ECS 1 Alarm UA 3 UANN003000 1 171 00 000
Voice Aux ECS 1 Alarm Restore UH 3 UHNN003000 3 171 00 000
Voice Aux ECS 2 Alarm UA 4 UANN004000 1 172 00 000
Voice Aux ECS 2 Alarm Restore UH 4 UHNN004000 3 172 00 000
Voice Aux ECS 3 Alarm UA 5 UANN005000 1 173 00 000
Voice Aux ECS 3 Alarm Restore UH 5 UHNN005000 3 173 00 000
Voice Aux ECS 4 Alarm UA 6 UANN006000 1 174 00 000
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID #
(If Any)
SIA
Event
Code
s
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.2 Report Formats Table (Continued)