IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 155
SIA – Panel Communicator Reporting
For examples see Table 11.4.
Event
Report
Zone/Point
Panel ID
PP
Module
MM
Zone
ZZZZ
Point
ZZZZ
Fields Sent
SIA Event
Data
Fire Alarm-Zone Zone 32 n/a 15 n/a EE-PP-MM-ZZZZ FA32000015
Fire Alarm-Zone Zone 32 n/a 05 n/a EE-PP-MM-ZZZZ FA32000005
Fire Alarm-Point Point 32 01 n/a 123 EE-PP-MM-ZZZZ FA32010123
Fire Alarm-Point Point 21 33 n/a 203 EE-PP-MM-ZZZZ FA21330203
Expander Trouble n/a 15 11 n/a n/a EE-PP-MM-ZZZZ ET15110000
Auto Test n/a 32 n/a n/a n/a EE-PP-MM-ZZZZ RP32000000
Battery Trouble-Panel 32 n/a 32 98 n/a n/a EE-PP-MM-ZZZZ YT32980000
Battery Trouble-Expander 18 n/a 32 18 n/a n/a EE-PP-MM-ZZZZ YT32180000
SLC Loop Shorted n/a 01 44 n/a n/a EE-PP-MM-ZZZZ ET01440000
Program Begin n/a 32 n/a n/a n/a EE-PP-MM-ZZZZ LB32000000
Program Begin n/a 22 n/a n/a n/a EE-PP-MM-ZZZZ LB22000000
AC Power Loss- Panel 22 n/a 22 98 n/a n/a EE-PP-MM-ZZZZ AT22980000
MM = 00
Fire Trouble Point 22 97 n/a 200 EE-PP-MM-ZZZZ FT22970200
Fire Trouble Zone 22 97 1 n/a EE-PP-MM-ZZZZ FT22970001
MM = 00
Fire Trouble-NAC Point 22 98 n/a NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007
ZZZZ=Pt. #
Fire Trouble-NAC Zone 22 98 n/a NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007
ZZZZ=OPG #
Table 11.4 SIA Reporting Examples