Revision 6 HC900 Process & Safety Controller User and Installation Manual 223
21 April 2017
8 Point Analog Input
Step
Action
1 2 3 7 8 94 5 6 10 11 12 13 17 18 1914 15 16 20
21 22 23 27 28 2924 25 26 30 31 32 33 37 38 3934 35 36 40
Input 1 Input 2 Input 3 Input 4
Input 6
Input 7
Input 8
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Input 5
Slidewire
Slidewire
R
F
R
F F F
F
F
F
F
R
R
R R
R
R
Note:
You must set switches 1- 8
for Ohms.
1 2 3 7 8 94 5 6 10 11 12 13 17 18 1914 15 16 20
21 22 23 27 28 2924 25 26 30 31 32 33 37 38 3934 35 36 40
1 2 3 7 8 94 5 6 10 11 12 13 17 18 1914 15 16 20
21 22 23 27 28 2924 25 26 30 31 32 33 37 38 3934 35 36 40
Input 1 Input 2 Input 3 Input 4
Input 6
Input 7
Input 8
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Slidewire
Input 5
Slidewire
Slidewire
R
F
R
F F F
F
F
F
F
R
R
R R
R
R
Note:
You must set switches 1- 8
for Ohms.
Figure 103 Slidewire feedback connections for actuators
Analog Input accuracy specification
Range
AI Module Accuracy
RTP + Cable Accuracy
AI Module + RTP
Accuracy
100 Plat. RTD
0.1% of Range
0.04% Range (0.357C)
0.14% of Range
JIS RTD
0.1% of Range
0.12% Range (0.824C)
0.22% of Range
10 Cu. RTD
0.1% of Range
0.57% Range (1.540C)
0.67% of Range
200 OHMS
0.1% of Range
0.07% Range (0.140)
0.17% of Range
0-10mV LINEAR
0.1% of Range
0.04% Range (0.004mV)
0.14% of Range

Table of Contents

Other manuals for Honeywell HC900