236 HC900 Process & Safety Controller User and Installation Manual Revision 6
21 April 2017
16 Point DC Digital Output
Step
Action
2
Mount RTP to DIN rail.
Latch to rail. See page 253.
Connect cable to RTP
3
Set/verify jumper positions as shown.
Jumper open
Jumper closed
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 83.
ATTENTION: SW1 only disconnects the positive terminal, not both sides of the DC power.
See page 240 for RTP internal schematic.