In the maintenance picture Service/Maintenance/Maintenance Compr. you will find the follow-
ing information:
Service counter
The total number of hours this compressor has been running since the last main C service has
been performed.
Main service C
The calculated estimated number of running hours between the two main C services.
If manual service is selected Main service C is set equal to Service interval C.
If automatic service is selected Main service C is calculated on the basis of how the compres-
sor has been operating since last main service, i.e. discharge pressure, suction pressure, ro-
tating speed and the number of starts/stops.
Next main service C
This is the calculated estimated number of running hours until the compressor needs the next
main service C.
This service interval is calculated as Main service C minus the running hours since last service
C.
Next sub-service B
This is the calculated estimated number of running hours until the compressor needs the next
service B. If next sub-service B is scheduled to be performed at the same time as the Main
service, the sub-service B will not be shown. The service B hour field will be blank, i.e. “--”.
This sub-service interval is calculated as Main service C / 2 minus the running hours since last
service B.
Next sub-service A
This is the calculated estimated number of running hours until the compressor needs the next
service A. If next sub-service A is scheduled to be performed at the same time as the Main
service or the sub-service B, the sub-service A will not be shown. The service A hour field will
be blank, i.e. “--”.
For screw compressors, this sub-service interval is calculated as Main service C / 6 minus the
running hours since last service A.
For reciprocating compressors this sub-service interval is calculated as Main service C / 4 mi-
nus the running hours since last service A.
Service
148/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals