2.1.6 Measured/calculated pressure levels/temp. - HPO/HPC
Measuring Min. Max. Factory Note
Suction pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
-
1.5
-1.0
-1.0
-
25.0
25.0
25.0
-
10.0
3.5
2.5
-
3+4+5
3+4+5
3+4+5
Discharge pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-
-1.0
45.0
44.0
-
-1.0
35.0
33.0
-
-1.0
1+6
1+6
-
1+5
Oil pressure (bar)
Calculated value
SMC100/TSMC/HPC
High shutdown
High alarm
Low alarm
Low shutdown
Low-low shutdown
5.0
5.0
0.5
0.5
0.0
7.0
7.0
5.0
5.0
1.5
6.0
5.5
4.0
3.5
0.5
2+5+16
2+5
2+5+14
2+5+14
2+5+32
Diff. pressure across oil filter
(bar)
Calculated value
SMC100/TSMC/HPC
High shutdown
High alarm
Low alarm
Low shutdown
0.0
0.0
-
-
8.0
5.0
-
-
6.0
4.0
-
-
2+11a
2+11a
-
-
High diff. pressure
Pc - Pe (bar)
Calculated value
High shutdown
High alarm
-
-
-
-
26.0
25.2
1+15
-
Discharge temperature
(°C)
High shutdown
High alarm
Low alarm
Low shutdown
60.0
50.0
-65.0
-
170.0
170.0
-65.0
-
160.0
155.0
-65.0
-
1+6
1+6
-
-
Oil temperature
(°C)
High shutdown
High alarm
Low alarm
Low shutdown
40.0
30.0
0.0
0.0
105.0
105.0
70.0
70.0
80.0
75.0
45.0
40.0
2+24
2+24
2+7+24
2+7+24
Process out temperature
(°C)
High shutdown
High alarm
Low alarm
Low shutdown
-20
-20
-20
-20
100.0
100.0
100.0
100.0
75.0
70.0
4.0
2.0
1+6
1+6
1+6
1+6
Process in temperature
(°C)
High shutdown
High alarm
Low alarm
Low shutdown
-60
-60
-100
-100
100.0
100.0
100.0
100.0
60.0
50.0
4.0
2.0
1+6
1+6
1+6
1+6
Suction gas superheat
(°C)
Calculated value
High shutdown
High alarm
Low alarm
Low shutdown
6.0
5.0
0.0
0.0
120.0
120.0
40.0
40.0
110.0
100.0
4.0
2.0
2+7
2+7
2+10+13
2+10+13
Discharge gas superheat
(°C)
Calculated value
Low alarm
Low shutdown
5.0
0.0
40.0
40.0
10.0
0.0
2+10+13
2+10+13
Table 14: Measured and calculated pressure levels and temperatures - HPO/HPC
Measuring Min. Max. Factory Note
User input 1
(4-20 mA)
High shutdown
High alarm
Low alarm
Low shutdown
-999.9
-999.9
-999.9
-999.9
999.9
999.9
999.9
999.9
0.0
0.0
0.0
0.0
3+18
3+18
3+18
3+18
Table 15: 4-20 mA User input 1 signal
Alarms and shutdowns
42/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals