5.1.4 Remote monitoring
A Remote Monitoring E-mail function has been introduced in Unisab III. This function enables
Unisab III to report compressor operation and events i.e. trend files, shutdowns and alarms
for central remote monitoring.
This picture shows the set-up parameters for Remote Monitoring. Remote monitoring must be
set to Yes to enable Trend and Events to the remote monitor server.
Note: Before Remote mon. can be configured to Yes the Remote monitoring functionality
must have been previously activated. See subsection 6.6.5. Function interface.
Service/Remote monitoring
No. Function Use Choices
1 Remote monitoring 1/2 No, Yes
2
Retries
(max. no of monitor and user mail re-
tries)
1/2 3, [1-10]
3 Port (SMTP port no.) 1/2 25, [1-32000]
4 Heartbeat 1/2 4, [1-24]
5
Alarm
(enable Alarm info to remote monitoring)
1/2 No, Yes
6
Max. hour
(max. no. of event mails per hour)
1/2
30, [1-120]
With the default setting 30, the mini-
mum time to elapse between two con-
secutive event mails will be 60/30 = 2
minutes.
7
Last e-mail
(status information for last sent e-mail)
1/2
Nothing sent, Success, Invalid Sender,
Invalid recipient, No connection, DNS
error, Authentication method, Authen-
tication failed, Discarded
Service
152/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals