6.4.4 Plant
The Plant menu includes set-up for the refrigeration plant. Some points are used for sequenc-
ing. COP and chiller set-up is also carried out here.
1: Refrigerant
Not defined
R717
R22
R502
R23
R404A
R134A
R507
R410A
R407C
R744
R1270
R290
R000
For R717 (and all other refrigerants) the converted pressure is always shown as dew point
values. Before the user-defined refrigerant R000 is chosen, the refrigerant curve must be en-
tered in picture Setup/Configuration/R000. See also subsection 3.5.13. Refrigerant R000.
2: Compr.
This number must be entered into Unisab III. The compressor has then been "named". Two
compressors must never have the same Compr. number.
3: Start
This number must be entered into Unisab III. This is this compressor's start number in the
Multisab sequencing system. Two compressors must not have the same start number on the
same Multisab System.
4: System
This number must be entered into Unisab III. This is this compressor's system number in the
Multisab sequencing system. It indicates which Multisab sequencing system this particular
compressor is assigned to. Two or more compressors may have the same system number.
Set-up
Engineering manual - Unisab III 1.10
001930 en 2014.09
187/319

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals