3.1.8 Regulation of reciprocating compressors
Reciprocating compressors are capacity regulated in stages by connection/disconnection of
cylinders, typically in pairs, through solenoid valves controlled by Unisab III.
How fast the compressor loads/unloads stages is determined by the timers Delay up and De-
lay down, which will start counting as soon as the value is outside the neutral zone. The regu-
lator is allowed to have a P Band of 0, which means that the stages are loaded in seconds as
set.
If the P band is above 0, the delay times can be prolonged as long as the value is within the P
band. The P band is only relevant if the P band factors Delay up and/or Delay down are set in
the picture P band factor at a value above 1. See P band factor in section 6.5. Timers.
If the value is just outside the neutral zone and the P band factor Delay up is e.g. 10, count-
ing will be slow: “1 sec.” becomes 10 sec. If the value is just outside the P Band, counting will
be speeded up, "1 sec." becomes 1 sec.
For reciprocating compressors connected to frequency converters see also the Unisab III se-
quence manual.
Compressor control and surveillance
70/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals