1.2.5 Session
When selecting the menu Session, the following picture appears:
Fig. 5: Session menu
Password
When you want to change a parameter you must enter a four digit password.
In Unisab III there are 4 password levels:
• Monitoring (no password) - monitoring access only
• User - access to change set points linked to normal operation
• Superuser - access to change configuration and critical set points
• Supervisor - Johnson Controls Denmark supervisor level
Switch between the password levels with
and . Choose the appropriate level with and
enter the four digit password using the arrow keys. When you have entered the four digits,
press
and then
F3
/OK.
If the password is accepted you will return to the picture where you wanted to change a pa-
rameter and may change the parameter value with the and keys.
In subsection 1.2.6. Changing set values, you will find a detailed example of how to change a
parameter, e.g. a limit value.
You can always log into Unisab III even if you are not prompted for a password. Simply
choose Current user in the Password picture in the Session menu.
In the Password menu you can inactivate an open password like this: Choose Current user in
the Password picture. The password “Lock” in the info bar will close and the password access
will be terminated.
Unisab III control
26/319
Engineering manual - Unisab III 1.10
001930 en 2014.09