2.1.2 Measured and calculated pressure levels - screws
Measuring Min. Max. Factory Note
Suction pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
-
1.5
-1.0
-1.0
-
9.0
6.0
6.0
-
5.0
1.5
1.0
-
3+4+5
3+4+5
3+4+5
Suction pressure (bar)
SAB 157HR
High shutdown
High alarm
Low alarm
Low shutdown
-
5.0
-1.0
-1.0
-
22.0
20.0
20.0
-
19.0
3.5
2.5
-
3+4+5
3+4+5
3+4+5
Internal suction pressure
(bar)
SAB 109-133-159 and SABflex
High shutdown
High alarm
Low alarm
Low shutdown
2.0
2.0
-
-
7.0
7.0
-
-
7.0
6.3
-
-1.0
2+26
2+26
-
Internal pressure (bar)
Calculated value
SAB 157HR
High shutdown
High alarm
Set point 1
Set point 2
-
-
-
-
-
-
-
-
100.0
-
80.0
75.0
2+29
Pressure ratio (II)
Calculated value
SAB 109-133-159 and SABflex
High shutdown
High alarm
1.0
1.0
50.0
50.0
30.0
25.0
1+6+27
1+6+27
Discharge pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-
-1.0
24.5
24.0
-
-1.0
16.0
15.0
-
-1.0
1+6
1+6
-
1+5
Discharge pressure (bar)
SAB 157HR
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-
-1.0
53.3
52.8
-
-1.0
52.0
50.0
-
-1.0
1+6
1+6
-
1+5
Oil pressure (bar)
Calculated value
SAB Mk 1 compressors
Low alarm
Low shutdown
1.5
1.0
6.0
5.0
4.0
2.5
2+7
2+7
Oil pressure (bar)
Calculated value
SAB Mk 2 compressors
Low alarm
Low shutdown
0.0
0.0
6.0
5.0
0.0
0.0
2+9
2+9
Oil pressure (bar)
Calculated value
SAB Mk 3, Mk 4 compressors
SAB 202, 283 Mk1, 330, 355
Mk1, FV 19, SV 24/26, FV
24/26
Low alarm
Low shutdown
Set point 1
Set point 2
1.0
0.5
0.0
0.0
6.0
5.0
10.0
10.0
1.5
1.2
2.5
4.0
2+9
2+9
21
21
Oil pressure (bar)
Calculated value
VMY Mk 2-2.5 compressor
Low alarm
Low shutdown
1.5
1.0
6.0
5.0
2.0
1.5
2+9+17
2+9+17
Oil pressure (bar)
Calculated value
VMY Mk 3 compressors
Low alarm
Low shutdown
Set point 1
Set point 2
1.5
1.0
0.0
0.0
6.0
5.0
10.0
10.0
4.0
3.0
5.5
7.0
2+9
2+9
22
22
Oil pressure (bar)
Calculated value
SAB 120-151, SAB 157HR and
SAB 193-233-283-355
Low alarm
Low shutdown
Set point 1
Set point 2
1.5
1.0
0.0
0.0
6.0
5.0
10.0
20.0
1.5
1.0
2.5
3.0
2+9b
2+9b
21
21
Alarms and shutdowns
Engineering manual - Unisab III 1.10
001930 en 2014.09
37/319

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals